DHS
home | People with disabilities | Publications & data | Design
for Safety | Minimum maintained average illuminance
Minimum maintained
average illuminance
Worksite Redesign
Technical Advisory Project
|
Ambient Light in
|
Task Light in
|
| Areas |
Lux |
Footcandles |
Lux |
Footcandles |
| Exterior Entrance
(Night) |
100 |
10 |
|
|
| Interior Entry
(Day) |
1000* |
100* |
|
|
| Interior Entry
(Night) |
100 |
10 |
|
|
| Exit Stairways
and Landings |
300 |
30 |
|
|
| Elevator Interiors |
300 |
30 |
|
|
| Parking Garage
Entrance |
500 |
50 |
|
|
| Exterior Walkways |
50 |
5 |
|
|
| |
|
|
|
|
| Administration
(Active) |
300 |
30 |
500 |
50 |
| Active Areas (Day
Only) |
300 |
30 |
500 |
50 |
| Visitor Waiting
(Day) |
300 |
30 |
|
|
| Visitor Waiting
(Night) |
100 |
10 |
|
|
| |
|
|
|
|
| Resident Room |
|
|
|
|
Entrance
|
300 |
30 |
|
|
Living Room
|
300 |
30 |
750 |
75 |
Bedroom
|
300 |
30 |
750 |
75 |
Wardrobe/Closet
|
300 |
30 |
|
|
Bathroom
|
300 |
30 |
|
|
Make-up/Shaving
Area
|
300 |
30 |
600 |
60 |
Shower/Bathing Area
|
300 |
30 |
|
|
Kitchen Area
|
300 |
30 |
500 |
50 |
|
|
|
|
|
| Barber/Beautician |
500 |
50 |
|
|
| Chapel or Quiet
Area (Active) |
300 |
30 |
|
|
| Hallways (Active
Hours) |
300 |
30 |
|
|
| Hallways (Sleeping
Hours) |
100 |
10 |
|
|
| Dining (Active
Hours) |
500 |
50 |
|
|
| |
|
|
|
|
| Medicine Preparation |
300 |
30 |
1000 |
100 |
| Nurses Station
(Day) |
300 |
30 |
500 |
50 |
| Nurses Station
(Night) |
100 |
10 |
500 |
50 |
| Physical Therapy
Area (Active Hours) |
300 |
30 |
500 |
50 |
| Occupational Therapy
(Active Hours) |
300 |
30 |
500 |
50 |
| Examination Room
(Dedicated) |
300 |
30 |
1000 |
100 |
| |
|
|
|
|
| Janitor's Closet |
300 |
30 |
|
|
| Laundry (Active
Hours) |
300 |
30 |
500 |
50 |
| Clean/Soiled Utility |
300 |
30 |
|
|
| Commercial Kitchen |
500 |
50 |
1000 |
100 |
| Food Storage (Non-Refrigerated) |
300 |
30 |
|
|
| Staff Toilet Area |
200 |
20 |
600 |
60 |
*Utilization of daylight is encouraged in entryways to provide a transition between
outside and interior illumination levels.Note: Ambient light levels
are minimum averages measured at 76 cm (30 in.) above the floor in a horizontal
plane. Task light levels are absolute minimums taken on the visual task.
For make-up/shaving, the measurement is to be taken on the face in a vertical
position.Note: It should be understood
that the values listed are minimums. The optimum solution for task lighting
is to give users control over the intensity and positioning of the light
source to meet their individual needs.
Return to top